1 Attachment #11 - Updated Engineering Service Report, Jewell Engineering, Oct 2017

2 PROCTOR PARK CONDOMINIUMS BRIGHTON, ONTARIO ENGINEERING SERVICING REPORT Municipality of Brighton County of Northumberland October 4, 2017 Prepared by Jarrod Gliddon, EIT Submitted by Steve Harvey, P.Eng.

3 Table of Contents 1 BACKGROUND EXISTING USE SITE DESCRIPTION SERVICING DEVELOPMENT ENVIRONMENTAL COMPLIANCE TRANSPORTATION SYSTEM WATER DISTRIBUTION SYSTEM SANITARY SEWER SYSTEM STORM SEWER SYSTEM REFERENCES CONCLUSION... 7 Appendices Appendix 1: Site Plans Appendix 2: Storm Sewer Design Sheets Appendix 3: Sanitary Sewer Design Sheets

4 1 Background G.D. Jewell Engineering Inc. (GDJE) has been retained by Ontario Limited to complete a servicing study to review the feasibility of a proposed condominium development, known as Proctor Park Condominiums located at 74 and 62 Young Street in Brighton, Ontario. The proposed site concept plan is provided in Appendix 1. This servicing design report has been prepared to support the re zoning and Official Plan Amendment application for Lots 7 and 10, West of Young Street, Registered Plan 28 and Part of Lot 1 Concession 2 as shown below in Figure 1. Figure 1: Project Location Currently there is full servicing (road, storm sewer, watermain and sanitary sewer) available along Young Street. The extent to which these services need to be extended to accommodate this development land is the focus of this report. Engineering Services Report 1 October 4, 2017

5 The condominium development proposal includes eighteen (18) condominium units, one (1) storm sewer service, one (1) sanitary sewer service, one (1) watermain service and one (1) driveway entrance. GDJE has summarized the overall servicing of the development in this report. The following services have been considered. Environmental Compliance Transportation System Water Distribution System Sanitary Sewer System Storm Sewer System 1.1 Existing Use The proposed development area is approximately 0.41 ha in area. The entire parcel of land is classified as low density residential according to the Municipality of Brighton s Official Plan. Rezoning and Official Plan Amendment applications will be required to permit the proposed medium density residential development. 1.2 Site Description The proposed development land is Lots 7 and 10, West of Young Street, Registered Plan 28 and Part of Lot 1 Concession 2 in the Municipality of Brighton. The southern boundary is approximately 190 metres north of Dorman Street. The west boundary is approximately 35 metres east from North Drive. The eastern boundary abuts Young Street. The northern boundary is approximately 60 metres south of the entrance to Proctor Park Conservation Area. There are several mature trees along the boundaries and southern portion of the property area. The topography has a natural flow southerly towards Proctors Creek which outlets into Lake Ontario. 2 Servicing 2.1 Development The proposed development is infill to an existing residential area. The proposed development includes eighteen (18) condominium units, one (1) storm sewer service, one (1) sanitary sewer service, one (1) watermain service and one (1) driveway entrance. Engineering Services Report 2 October 4, 2017

6 2.2 Environmental Compliance An Environmental Impact Study (EIS) has been completed by Eco Site Assessors Inc. The EIS shows the proposed development is unlikely to cause any significant environmental impact to the features and functions of the surrounding environment through the following minor provisions: 1. All construction debris and waste materials will be promptly removed from the Site and deposited at authorized receiving sites. 2. Given the wetland identified on topographic mapping for the Site and the type of mature trees growing on the property that thrive wet conditions, the planned removal of these mature trees may result in increased volumes of surface water requiring management. 3. Develop and Erosion and Sediment Control Plan for the construction phase of the development. 4. Develop a Spill Control and Response Plan for the construction phase of the development. 5. Post development, stormwater from roofs, access roads and parking areas should be directed away from neighbouring residential properties. 2.3 Transportation System Access to the residential condominium units will be provided by one (1) driveway entrance and parking lot off of Young Street. The driveway entrance and parking lot area will be fully paved and provide adequate access for emergency services. Access to the development is proposed from Young Street (County Road 30) which connects the rural environs to the Municipality and the Central Business District (CBD). Residential and commercial properties have direct access to the corridor. Young Street has been recently reconstructed in the past three (3) years and accommodates two traffic flow lanes and bike lanes on both sides. Other features of Young Street include, curbs, street lighting and a sidewalk on the east side of the street. In the study area, side streets intersecting Young Street operate with stop sign control. The posted speed on this section of Young Street is 50 km/hr. The minimum sight distances for the location were reviewed assuming a design speed of 60km/hr. The minimum stopping sight distance according to Table C2 1 in the Geometric Design Standards for Ontario Highways for wet roadway conditions for a design speed of 60km/hr is 85m. The minimum stopping sight distance is greater than 85m for this location and therefore meets the design criteria. Currently the roadway is marked as no passing with a solid yellow centerline. Engineering Services Report 3 October 4, 2017

7 GDJE has completed a Traffic Impact Study (TIS), which is attached under a separate cover, shows the proposed development will have no significant impacts on traffic for the surrounding area, or the level of service of Young Street. 2.4 Water Distribution System An existing 300mm diameter PVC watermain is servicing Young Street. The existing watermain has recently been installed as part of the Young Street reconstruction project which was completed in The static pressure in the watermain is assumed to meet current design standards. GDJE recommends a 150mm diameter service to the condominium development. The watermain design criteria used are based on Ministry of Environment (MOE) guidelines and are summarized below. Average Residential Daily Domestic Demand: 450L/cap.day Max Hourly Demand Pressure Minimum: 40 psi Max Day + Fire Flow Demand Pressure Minimum: 20 psi The domestic flows are estimated by multiplying the average residential daily domestic demand by the amount of people within the development. We estimated 2.4 people per unit within the 18 unit condominium creating a total of 44 people within the development and resulting in a domestic flow of 19,800L/day or 0.23L/s. The maximum day demand is found by multiplying the domestic flow by a peaking factor, in this case 2.75, resulting in a Max Day Demand of 0.63L/s. Since existing fire hydrants in the area are within maximum allowable distances to the development it is not required to install a fire hydrant on site and therefore fire flows can be ignored. The Max Day + Fire Flow design check is therefore kept at 0.63L/s and can result in a service as small as two inches or 50mm in diameter, however it is recommended to install a 150mm diameter service to accommodate detailed design options of water pressure within the condominium. 2.5 Sanitary Sewer System An existing 200mm diameter PVC gravity sanitary sewer is servicing Young Street. The existing sanitary sewer has recently been installed as part of the Young Street reconstruction project which completed in 2016 and provides adequate capacity for the condominium development. Engineering Services Report 4 October 4, 2017

8 The existing 200mm sanitary sewer is at approximately 4.54% with an approximate invert of m at the entrance to 74 Young Street. GDJE recommends a 125mm sanitary sewer at approximately 2.0% slope to service the condominium development. The total design flow of the development, which determines the impact of the existing sewer is 1.1 L/s. The sanitary design criteria used are based on Ministry of Environment (MOE) guidelines and are summarized below. Average Daily Residential Domestic Flows: 450L/cap.day Extraneous Flow Allowance: 0.28L/ha.s Minimum Full Flow Velocities: 0.6m/s Maximum Full Flow Velocities: 3.0m/s Population Factor: 2 Bedroom Condominium 2.4 persons/unit A sanitary sewer design sheet has been attached to this report in Appendix 3. correspondence from the Municipality affixed in Appendix 4 confirms the proposed flows can be accommodated by the current system. 2.6 Storm Sewer System An existing 450mm diameter HDPE gravity storm sewer is servicing Young Street. The existing storm sewer has recently been installed as part of the Young Street reconstruction project which completed in 2016 and provides adequate capacity for the condominium development. The existing 450mm storm sewer is at approximately 2.3% with an approximate invert of m at the entrance to 74 Young Street. GDJE recommends that the site be graded so that all hardened surfaces (ie building, concrete and asphalt) drain into two 600mm x 600mm catch basins located in the parking lot. A 300mm storm sewer at approximately 1.0% slope will connect the catch basins and service the condominium development. The 300mm service will then connect into the storm sewer along Young Street. The total design flow of the development, which determines the impact of the existing sewer is approximately 80 L/s. Any expressed concerns to handle surface drainage will be accommodated through our runoff coefficient selection. The grassed areas will drain as per pre development conditions. A stormwater management letter with further information was completed. Engineering Services Report 5 October 4, 2017

9 GDJE have checked the storm water capacity within the Municipal infrastructure adjacent to the site to determine in the Municipal storm infrastructure can accommodate the development. Catchment areas contributing to the system were delineated using contours from OFAT III and runoff coefficients were estimated using Design Chart 1.07 of the MTO Drainage Manual. We have attached a storm sewer design sheet and a catchment area drawing that shows there is adequate capacity in the recently re constructed storm sewer system existing on Young Street. Catchment 106B is represented by the dashed line and is to drain south of the Walas development as per current condition. The existing storm sewer on Young Street provides adequate capacity for the condominium development. 2.7 References The information used to prepare this Report is based on the following documents and information provided as noted below. Municipality of Brighton Young Street Reconstruction Construction Drawings dated April 2015 Site Plan, dated January 2017 Municipality of Brighton Zoning Bylaw Maps Municipality of Brighton Official Plan, dated April 23, 2014 Municipality of Brighton Zoning By Law # , dated December 16, 2002 Design Guidelines for Sewage Works, 2007, Ontario Ministry of Environment Design Guidelines for Drinking Water Systems, 2007, Ontario Ministry of Environment Geometric Design Guide for Canadian Roads, dated September 1999 Engineering Services Report 6 October 4, 2017

10 3 Conclusion G.D. Jewell Engineering studied the proposed development and have the following conclusions: 1. The proposed development concept provides no significant impact to traffic. 2. There is sufficient watermain pressure to service the development site concept. GDJE recommends a 150mm diameter watermain to tee into the existing 300mm watermain along Young Street to service the proposed development. 3. There is sufficient sanitary sewer capacity to service the development site concept. GDJE recommends a 125mm diameter PVC sanitary sewer to tee into the existing 200mm sanitary sewer along Young Street to service the proposed development. 4. There is sufficient storm sewer capacity to service the development site concept. GDJE recommends a 300mm diameter storm sewer to tee into the existing 450mm storm sewer along Young Street to service the proposed development. GDJE recommends the hard surfaces drain into two catch basins, while the grassed areas drain as per predevelopment conditions. In conclusion, the proposed development and all other site plan options provided in this report are serviceable in conjunction with the recommendations within this report. Prepared by: Submitted by: Jarrod Gliddon, EIT Steve Harvey, P.Eng. G.D. Jewell Engineering Ltd. G.D. Jewell Engineering Ltd. Engineering Services Report 7 October 4, 2017

11 APPENDIX 1 SITE PLAN Engineering Services Report September 22, 2017

12

13 CONSULTING ENGINEERS KINGSTON BELLEVILLE MISSISSAUGA TEL: (613) FAX: (613) TEL: (613) FAX: (613) TOLL FREE TEL: (905) FAX: (905) MARK WALAS 74 YOUNG STREET STORM SEWER REVIEW CATCHMENT AREAS 1

14 APPENDIX 2 STORM SEWER DESIGN SHEETS Engineering Services Report September 22, 2017

15 STORM SEWER DESIGN SHEET Pipe Capacity by Manning's Equation Peak Runoff Estimate by Rational Method Intensity for Trenton Where: Where: 5 Year Parameters A = area of pipe in m 2 Check Q = Peak Flow in cms A = 24.8 Manning's Coef R = Hydraulic radius = A / P C = Runoff Coefficient Where: B = CSP P = Wetted perimeter i = Rainfall Intensity in mm/hr i = Rainfall Intensity in mm/hr RCP/PVC S = Slope (m/m) V 6 / A = Area in hectares T c = Time of Concentration in minutes n = Manning's friction coef. LOCATION PEAK FLOW CALCULATION PROPOSED SEWER R.C. x A CUM. R.C TIME OF INTENSITY PEAK Pipe Size Length Type of Grade (use Capacity, Full Flow CATCHMENT AREAS x A CONCENTRATI FLOW Pipe m/m) n = Velocity STREET FROM TO RUNOFF COEFFICIENT ON ha ha min mm/hr m 3 /s (mm) (m) (%) (m 3 /s) (m/s) min (m/s) 74 Young Street CB1 CB PVC 1.00% OK CB2 CB PVC 1.50% OK CB3 Ex Storm PVC 1.00% OK Time of Flow Actual Velocity at Q d Check Capacity G.D. Jewell Engineering Inc Ph Designed: Jarrod Gliddon, EIT 1 71 Millennium Parkway Fx Checked: Steve Harvey, P.Eng. Belleville, ON, K8N 4Z5 Date: Thursday, April 06, 2017 Project: 74 Young Street, Brighton, Ontario 5 Year Storm Event

16 STORM SEWER DESIGN SHEET Pipe Capacity by Manning's Equation Peak Runoff Estimate by Rational Method Intensity for Trenton Where: Where: 100 Year Parameters A = area of pipe in m 2 Check Q = Peak Flow in cms A = 42.5 Manning's Coef R = Hydraulic radius = A / P C = Runoff Coefficient Where: B = CSP P = Wetted perimeter i = Rainfall Intensity in mm/hr i = Rainfall Intensity in mm/hr RCP/PVC S = Slope (m/m) V 6 / A = Area in hectares T c = Time of Concentration in minutes n = Manning's friction coef. LOCATION STREET FROM TO CATCHMENT AREAS RUNOFF COEFFICIENT PEAK FLOW CALCULATION R.C. x A CUM. R.C x A TIME OF CONCENTRATI ON INTENSITY PEAK FLOW PROPOSED SEWER Capacity, n = ha ha min mm/hr m 3 /s (mm) (m) (%) (m 3 /s) (m/s) min (m/s) 74 Young Street CB1 CB PVC 1.00% OK CB2 CB PVC 1.50% OK CB3 Ex Storm PVC 1.00% OK Pipe Size Length Type of Pipe Grade (use m/m) Full Flow Velocity Time of Flow Actual Velocity at Q d Check Capacity G.D. Jewell Engineering Inc Ph Designed: 1 71 Millennium Parkway Fx Checked: Belleville, ON, K8N 4Z5 Date: Jarrod Gliddon, EIT Steve Harvey, P.Eng. Thursday, April 06, 2017 Project: 74 Young Street, Brighton, Ontario 100 Year Storm Event

17 STORM SEWER DESIGN SHEET Pipe Capacity by Manning's Equation Peak Runoff Estimate by Rational Method Q = 1 n A R2 3 S 1 2 Q = 1 C i A 360 Intensity for Trenton Where: Where: i = A TcB 5-Year Parameters A = area of pipe in m 2 Check Q = Peak Flow in cms A = 24.8 Manning's Coef R = Hydraulic radius = A / P C = Runoff Coefficient Where: B = CSP P = Wetted perimeter q Q i = Rainfall Intensity in mm/hr i = Rainfall Intensity in mm/hr RCP/PVC S = Slope (m/m) V 6 m/s A = Area in hectares T c = Time of Concentration in minutes HDPE n = Manning's friction coef. LOCATION PEAK FLOW CALCULATION PROPOSED SEWER R.C. x A CUM. R.C TIME OF INTENSITY PEAK Pipe Size Length Type of Grade (use Capacity, Full Flow CATCHMENT AREAS x A CONCENTRATI FLOW Pipe m/m) n = Velocity STREET FROM TO RUNOFF COEFFICIENT ON ha ha min mm/hr m 3 /s (mm) (m) (%) (m 3 /s) (m/s) min (m/s) George Street 100 CB2 CBMH HDPE 4.10% OK 101 CBMH1 CBMH HDPE 2.60% OK 102 CBMH2 CBMH HDPE 1.40% OK 103 CBMH3 CBMH HDPE 1.25% OK Young Street 104 CBMH4 CBMH HDPE 2.90% OK 105 CBMH5 CBMH HDPE 3.30% OK 106A CBMH6 CBMH HDPE 2.20% OK Time of Flow Actual Velocity at Q d Check Capacity G.D. Jewell Engineering Inc Ph Designed: Elliott Fledderus, E.I.T Millennium Parkway Fx Checked: Bryon Keene, P. Eng. Belleville, ON, K8N 4Z5 Date: September Project: 74 Young Street, Brighton, Ontario 5 Year Storm Event

18 APPENDIX 3 SANITARY SEWER DESIGN SHEETS Engineering Services Report September 22, 2017

19 Peak Design Flow Calculation (Q d ) Peak Design Flow = (Q p ) Peak population flow + (Q i ) peak extraneous flow (L/s) SANITARY SEWER DESIGN SHEET Pipe Capacity by Manning's Equation Where: Population Flows (Persons/Unit) Where: q = Average daily per capita flow 450 L/Ca./Day Single Family 3.5 A = area of pipe in m 2 Check I = Unit of peak extraneous flow 0.28 L/s/ha Semi (3bdrm) 3.5 R = Hydraulic radius = A / P 0.8 M = Harmon peaking factor (min = 2) Semi (2bdrm) 2.4 P = Wetted perimeter 14 P = Population in 1000's Batchelor 1.6 S = Slope (m/m) A = Area in hectares n = Manning's friction coef. use Actual V if d:d< 0.3 LOCATION PEAK FLOW CALCULATION PROPOSED SEWER STREET FROM TO Peaking Pop. Flow Peak Ex. Design Length Pipe Size Type of Grade Capacity, Full Flow Ratio d:d Actual INDIVIDUAL CUMULATIVE Factor Flow Flow Pipe (use m/m) n = Velocity Velocity Area (A) Area (A) M Q( p ) Q( i ) Q( d ) at Q Pop. Pop. d (ha) (ha) (L/s) (L/s) (L/s) (m) (mm) (%) (L/s) (m/s) (m/s) Check PROPOSED DEVELOPMENT: Building Ex Young St PVC 2.00% OK 1 G.D. Jewell Engineering Inc Ph Single Family 3.5 Designed: Jarrod Gliddon, E.I.T Millennium Parkway Fx Bdrm Townhouses 3.5 Checked: Steve Harvey, P.Eng. Belleville, ON, K8N 4Z5 2 Bdrm Townhouses 2.4 Date: Thursday, April 06, 2017 Project: 74 Young Street, Brighton, Ontario

20 APPENDIX 4 CORRESPONDENCE Engineering Services Report September 22, 2017

21 Steve Harvey From: Sent: To: Cc: Subject: Keith Lee Tuesday, September 19, :24 PM Steve Harvey Lucas Kelly; Bryon Keene Re: 74 Young Street - Sanitary Capacity This is okay from my prospective, the sanitary as you was just updated, so this would not be an issue. KL Sent from my BlackBerry the most secure mobile device via the Bell Network From: Sent: September 19, :06 PM To: Cc: Subject: 74 Young Street - Sanitary Capacity Hi Keith, G.D. Jewell Engineering Inc. has been retained by Ontario Limited to complete a servicing study to review the feasibility of a proposed condominium development, known as Proctor Park Condominiums located at 74 and 62 Young Street in Brighton. The location plan is attached hereto. I m wondering if your sanitary system can accommodate the 1.1L/s of sanitary flow expected from the proposed development at 74 Young Street? Let me know if you need any additional information. Thank you,..steve Steve Harvey, P.Eng. G.D. Jewell Engineering Inc Millennium Parkway Belleville, ON K8N 4Z5 Phone Fax

UPDATED FUNCTIONAL SERVICING and STORMWATER MANAGEMENT REPORT

UPDATED FUNCTIONAL SERVICING and STORMWATER MANAGEMENT REPORT TRAFALGAR ENGINEERING LTD. #1-481 Morden Road Oakville Ontario L6K 3W6 UPDATED FUNCTIONAL SERVICING and STORMWATER MANAGEMENT REPORT Fernbrook Homes (Bronte 15) Limited 3059/3047 Lakeshore Road West TOWN

More information

89 Avenue Road GP Ltd. Functional Servicing and Stormwater Management Report for 89 Avenue Road Re-Development City of Toronto

89 Avenue Road GP Ltd. Functional Servicing and Stormwater Management Report for 89 Avenue Road Re-Development City of Toronto 89 Avenue Road GP Ltd. Functional Servicing and Stormwater Management Report for 89 Avenue Road Re-Development City of Toronto Prepared By: R.J. Burnside & Associates Limited 6990 Creditview Road, Unit

More information

SERVICING REPORT SITE PLAN AND PLAN OF CONDOMINIUM BLOCK 53 FERRIS DRIVE PLAN 58M-379 & PART OF LOT 4, REGISTERED PLAN 622 WELLESLEY, ONTARIO

SERVICING REPORT SITE PLAN AND PLAN OF CONDOMINIUM BLOCK 53 FERRIS DRIVE PLAN 58M-379 & PART OF LOT 4, REGISTERED PLAN 622 WELLESLEY, ONTARIO BLOCK 53 FERRIS DRIVE PLAN 58M-379 & PART OF LOT 4, REGISTERED PLAN 622 WELLESLEY, ONTARIO MARCH 2014 BLOCK 53 Ferris Drive Plan 58M-379 & Part of Lot 4, Registered Plan 622 WELLESLEY, ONTARIO DOCUMENT

More information

STORMWATER MANAGEMENT AND SERVICING REPORT IN SUPPORT OF SITE PLAN APPLICATION Cumberland Terrace

STORMWATER MANAGEMENT AND SERVICING REPORT IN SUPPORT OF SITE PLAN APPLICATION Cumberland Terrace STORMWATER MANAGEMENT AND SERVICING REPORT IN SUPPORT OF SITE PLAN APPLICATION Cumberland Terrace City of Toronto Toronto & North York District Prepared For: Oxford Properties Group 130 Adelaide Street

More information

Stormwater Management Functional Servicing Report

Stormwater Management Functional Servicing Report Stormwater Management Functional Servicing Report Part of Lot 12, Concession 10 Township of Cavan Monaghan Ian Cameron Rural Subdivision Engage Project No. 14016 Engage Engineering Ltd. January 7, 2015

More information

CHAPTER 2 HYDRAULICS OF SEWERS

CHAPTER 2 HYDRAULICS OF SEWERS CHAPTER 2 HYDRAULICS OF SEWERS SANITARY SEWERS The hydraulic design procedure for sewers requires: 1. Determination of Sewer System Type 2. Determination of Design Flow 3. Selection of Pipe Size 4. Determination

More information

Engineering Specifications February, 2004 Schedule H to Bylaw 7452, Subdivision Bylaw Page 18

Engineering Specifications February, 2004 Schedule H to Bylaw 7452, Subdivision Bylaw Page 18 Schedule H to Bylaw 7452, Subdivision Bylaw Page 18 3.4 Sanitary Sewers 3.4.1 Materials 3.4.1.1 The class and type of pipe and fittings, together with required class of bedding and trench widths, shall

More information

Functional Servicing and Storm Water Management Report. Project Location: 258 Sunview Street Waterloo, Ontario

Functional Servicing and Storm Water Management Report. Project Location: 258 Sunview Street Waterloo, Ontario 258 SUNVIEW STREET Functional Servicing and Storm Water Management Report Project Location: 258 Sunview Street Waterloo, Ontario Prepared for: 258 Sunview Inc. 815 Bridge Street West Waterloo, ON N2V 2M7

More information

ENGINEERING DESIGN GUIDELINES. for SUBDIVISIONS OR COMMERCIAL DEVELOPMENTS

ENGINEERING DESIGN GUIDELINES. for SUBDIVISIONS OR COMMERCIAL DEVELOPMENTS ENGINEERING DESIGN GUIDELINES for SUBDIVISIONS OR COMMERCIAL DEVELOPMENTS City of Birmingham Department of Planning, Engineering and Permits Engineering Division Office of the City Engineer 2008 TABLE

More information

SECTION 6A STORM DRAIN DESIGN Mar. 2002 S E C T I O N 6A STORM DRAIN - DESIGN

SECTION 6A STORM DRAIN DESIGN Mar. 2002 S E C T I O N 6A STORM DRAIN - DESIGN S E C T I O N 6A STORM DRAIN - DESIGN 6A.l Scope 6A.2 Storm Water Quantity 6A.3 Storm Drain Hydraulics 6A.4 Depths 6A.5 Locations 6A.6 Curved Storm Drains 6A.7 Manholes 6A.8 Catch basins 6A.9 Storm Drain

More information

629, 633 and 675 Eastern Avenue City of Toronto Toronto & East York District. Functional Servicing and Stormwater Management Report June 2013 13029

629, 633 and 675 Eastern Avenue City of Toronto Toronto & East York District. Functional Servicing and Stormwater Management Report June 2013 13029 629, 633 and 675 Eastern Avenue City of Toronto Toronto & East York District Functional Servicing and Stormwater Management Report June 2013 13029 Executive Summary This Functional Servicing and Stormwater

More information

Land Disturbance, Erosion Control and Stormwater Management Checklist. Walworth County Land Conservation Department

Land Disturbance, Erosion Control and Stormwater Management Checklist. Walworth County Land Conservation Department Land Disturbance, Erosion Control and Stormwater Management Checklist Walworth County Land Conservation Department The following checklist is designed to assist the applicant in complying with the Walworth

More information

FUNCTIONAL SERVICING AND STORMWATER MANAGEMENT REPORT

FUNCTIONAL SERVICING AND STORMWATER MANAGEMENT REPORT FUNCTIONAL SERVICING AND STORMWATER MANAGEMENT REPORT Proposed Residential and Commercial Development AT 177 Cross Avenue Town of Oakville Prepared for Salmona Tregunno Inc. Jun 18, 2012 REVISIONS 1 st

More information

CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT

CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT Page 1 CITY OF VAUGHAN SCHEDULE O LOT GRADING DESIGN FOR RESIDENTIAL DEVELOPMENT CIVIC CENTRE 2141 MAJOR MACKENZIE DRIVE MAPLE ONTARIO L6A 1T1 905-832-2281 Page 2 SECTION 1 - GENERAL OBJECTIVES To provide

More information

Storm Drainage Systems 11.9-1

Storm Drainage Systems 11.9-1 Storm Drainage Systems 11.9-1 11.9 Gutter Flow Calculations 11.9.1 Introduction Gutter flow calculations are necessary in order to relate the quantity of flow (Q) in the curbed channel to the spread of

More information

PUBLIC WORKS DESIGN, SPECIFICATIONS & PROCEDURES MANUAL LINEAR INFRASTRUCTURE

PUBLIC WORKS DESIGN, SPECIFICATIONS & PROCEDURES MANUAL LINEAR INFRASTRUCTURE REGION OF PEEL PUBLIC WORKS DESIGN, SPECIFICATIONS & PROCEDURES MANUAL LINEAR INFRASTRUCTURE Storm Sewer Design Criteria REVISED July 2009 PUBLIC WORKS STORM SEWER DESIGN CRITERIA TABLE OF CONTENTS 1.0

More information

HIGHWAY DEPARTMENT ACCESS AND RIGHT OF WAY WIDTH GUIDELINES

HIGHWAY DEPARTMENT ACCESS AND RIGHT OF WAY WIDTH GUIDELINES Approved 6/26/01 HIGHWAY DEPARTMENT ACCESS AND RIGHT OF WAY WIDTH GUIDELINES All new, modified and/or changed use access(es) onto county roads shall be subject to the access and corridor protection guidelines

More information

City of London South Street and Wellington Street Storm / Sanitary / Water Servicing Strategy

City of London South Street and Wellington Street Storm / Sanitary / Water Servicing Strategy City of London South Street and Wellington Street Storm / Sanitary / Water Servicing Strategy Prepared by: AECOM 410 250 York Street, Citi Plaza 519 673 0510 tel London, ON, Canada N6A 6K2 519 673 5975

More information

PLANNED UNIT DEVELOPMENT & SIDEWALK WAIVER REQUEST STAFF REPORT Date: November 7, 2013

PLANNED UNIT DEVELOPMENT & SIDEWALK WAIVER REQUEST STAFF REPORT Date: November 7, 2013 PLANNED UNIT DEVELOPMENT & SIDEWALK WAIVER REQUEST STAFF REPORT Date: November 7, 2013 NAME LOCATION Audubon Properties, LLC. 4700 & 4960 Dauphin Island Parkway West side of Dauphin Island Parkway, 580

More information

Basic Elements of Reading Plans

Basic Elements of Reading Plans Center for Land Use Education and Research at the University of Connecticut Basic Elements of Reading Plans University of Connecticut. The University of Connecticut supports all state and federal laws

More information

Module 6 : Quantity Estimation of Storm Water. Lecture 6 : Quantity Estimation of Storm Water

Module 6 : Quantity Estimation of Storm Water. Lecture 6 : Quantity Estimation of Storm Water 1 P age Module 6 : Quantity Estimation of Storm Water Lecture 6 : Quantity Estimation of Storm Water 2 P age 6.1 Factors Affecting the Quantity of Stormwater The surface run-off resulting after precipitation

More information

THE CORPORATION OF THE CITY OF GUELPH. THEREFORE the council of the Corporation of the City of Guelph enacts as follows:

THE CORPORATION OF THE CITY OF GUELPH. THEREFORE the council of the Corporation of the City of Guelph enacts as follows: THE CORPORATION OF THE CITY OF GUELPH By-law (1993)-14515 A by-law respecting storm water disposal from private property in the City of Guelph, to amend By-law (1987)-12602 and to adopt Municipal Code

More information

REGION OF PEEL PUBLIC WORKS DESIGN, SPECIFICATIONS & PROCEDURES MANUAL

REGION OF PEEL PUBLIC WORKS DESIGN, SPECIFICATIONS & PROCEDURES MANUAL REGION OF PEEL PUBLIC WORKS DESIGN, SPECIFICATIONS & PROCEDURES MANUAL LINEAR INFRASTRUCTURE Functional Servicing and Storm Water Management Report PUBLIC WORKS TABLE OF CONTENTS 1. INTRODUCTION...1 2.

More information

1. It would create hazardous effects of storm water run-off. 3. It would increase hazardous driving conditions on the public road.

1. It would create hazardous effects of storm water run-off. 3. It would increase hazardous driving conditions on the public road. SECTION 6: REQUIREMENTS FOR A DRIVEWAY CONNECTION A. Required information. The application shall be accompanied by a sketch of the proposed driveway which at a minimum shall indicate: 1. Geometric information

More information

Class Environmental Assessment Schedule B Project File Report

Class Environmental Assessment Schedule B Project File Report R.J. Burnside & Associates Limited 16775 Yonge Street Suite 200 Newmarket ON L3Y 8J4 Canada telephone (905) 953-8967 fax (905) 953-8945 web www.rjburnside.com Class Environmental Assessment Schedule B

More information

Stormwater Management Design Brief. Proposed Commercial Redevelopment 5830 Hazeldean Road Ottawa (Stittsville), Ontario.

Stormwater Management Design Brief. Proposed Commercial Redevelopment 5830 Hazeldean Road Ottawa (Stittsville), Ontario. Stormwater Management Design Brief Proposed Commercial Redevelopment 5830 Hazeldean Road Ottawa (Stittsville), Ontario Prepared For: 1319 Kanata Tires & Rims June 30, 2015 Report No: FS-15-013-REP.02 Stormwater

More information

CHAPTER 3 STORM DRAINAGE SYSTEMS

CHAPTER 3 STORM DRAINAGE SYSTEMS CHAPTER 3 STORM DRAINAGE SYSTEMS 3.7 Storm Drains 3.7.1 Introduction After the tentative locations of inlets, drain pipes, and outfalls with tail-waters have been determined and the inlets sized, the next

More information

CONTENT COPY OF ORIGINAL

CONTENT COPY OF ORIGINAL Ministry of the Environment Ministère de l Environnement Access Self Storage Inc. 100 Canadian Road Toronto, Ontario M1R 4Z5 AMENDED ENVIRONMENTAL COMPLIANCE APPROVAL NUMBER 8701-9A4QC7 Issue Date: August

More information

PART 6 - STANDARD DESIGN AND CALCULATION FORMS 6.1 SANITARY SEWER DATA SHEET

PART 6 - STANDARD DESIGN AND CALCULATION FORMS 6.1 SANITARY SEWER DATA SHEET PART 6 - STANDARD DESIGN AND CALCULATION FORMS 6.1 SANITARY SEWER DATA SHEET Name of Municipality or Sewer District Name of Project Original Township and Lot Number Name of Engineer of Firm Preparing Plans

More information

From Civil 3D, with Love

From Civil 3D, with Love From Civil 3D, with Love Download the zip file containing the files needed for the exercise. Extract the files to a convenient location on your hard drive before you begin. The files associated with this

More information

SUBDIVISION REQUIREMENTS SECTION 2 - DESIGN REQUIREMENTS INDEX

SUBDIVISION REQUIREMENTS SECTION 2 - DESIGN REQUIREMENTS INDEX SUBDIVISION REQUIREMENTS SECTION 2 - DESIGN REQUIREMENTS INDEX Page 2.00 INTRODUCTION... 1 2.01 STORM DRAINAGE... 2 2.01.01 Storm Sewer Design... 2 2.01.01.01 Run-off Calculations... 2 2.01.01.02 Storm

More information

PROJECT COST ESTIMATE ASSUMPTIONS AND EXCLUSIONS

PROJECT COST ESTIMATE ASSUMPTIONS AND EXCLUSIONS C PROJECT ESTIMATE ASSUMPTIONS AND EXCLUSIONS In support of the alternatives development process, preliminary cost estimates were prepared for each of the three Candidate Build Alternatives. The cost estimates

More information

SECTION 5 DRAFTING STANDARDS

SECTION 5 DRAFTING STANDARDS SECTION 5 DRAFTING STANDARDS 1 SECTION FIVE TABLE OF CONTENTS Description Page TABLE OF CONTENTS... 5-2 GENERAL... 5-3 DRAFTING STANDARDS... 5-5 DRAFTING MINIMUM REQUIREMENTS HANDOUT... 5-8 2 GENERAL 1.

More information

PUBLIC WORKS DESIGN, SPECIFICATIONS & PROCEDURES MANUAL LINEAR INFRASTRUCTURE

PUBLIC WORKS DESIGN, SPECIFICATIONS & PROCEDURES MANUAL LINEAR INFRASTRUCTURE REGION OF PEEL PUBLIC WORKS DESIGN, SPECIFICATIONS & PROCEDURES MANUAL LINEAR INFRASTRUCTURE Sanitary Sewer Design Criteria REVISED July 2009 PUBLIC WORKS SANITARY SEWER DESIGN CRITERIA TABLE OF CONTENTS

More information

8.1.3 General Design Guidelines. The following guidelines shall be used when designing inlets along a street section:

8.1.3 General Design Guidelines. The following guidelines shall be used when designing inlets along a street section: . Introduction Presented in this chapter are the criteria and methodology for design and evaluation of storm sewer inlets located in Town of Castle Rock. The review of all planning submittals will be based

More information

New Road 11.0m Asphalt 23m ROW

New Road 11.0m Asphalt 23m ROW New Road 11.0m Asphalt 23m ROW Granular A - 150 mm sq. m. $5.35 $69.53 Granular B - 300 mm sq. m. $7.35 $95.54 Concrete Curb and Gutter m. $44.67 $89.34 HL3 Asphalt - 40 mm sq. m. $7.66 $84.23 HL 4 or

More information

Micromanagement of Stormwater in a Combined Sewer Community for Wet Weather Control The Skokie Experience

Micromanagement of Stormwater in a Combined Sewer Community for Wet Weather Control The Skokie Experience Micromanagement of Stormwater in a Combined Sewer Community for Wet Weather Control The Skokie Experience Robert W. Carr 1 * and Stuart G. Walesh 2 1 Water Resources Modeling, LLC, 4144 S. Lipton Ave,

More information

Chapter 9 Sanitary Sewers

Chapter 9 Sanitary Sewers Chapter 9 Sanitary Sewers S:/Engineering/Design Standards/Chapter 9 12/29/2014 Section 9.1 Topic General Requirements Chapter 9 Sanitary Sewers Page 9-1 9.2 Plan Submittals 9-1 9.3 Determination of Flow

More information

PRELIMINARY STORMWATER MANAGEMENT AND SERVICING REPORT

PRELIMINARY STORMWATER MANAGEMENT AND SERVICING REPORT High Park Bayview Inc. c/o GWL Realty Advisors Inc. GRENADIER SQUARE DEVELOPMENT CITY OF TORONTO PRELIMINARY STORMWATER MANAGEMENT AND SERVICING REPORT LEA PROJECT #: 9114 NOV.2012 (REV. NOV. 2013) www.lea.ca

More information

Breslau Settlement Plan. Preliminary Servicing and Stormwater Management Report. December 2015. Prepared by:

Breslau Settlement Plan. Preliminary Servicing and Stormwater Management Report. December 2015. Prepared by: Breslau Settlement Plan Preliminary Servicing and Stormwater Management Report December 2015 Prepared by: SCS Consulting Group Ltd 30 Centurian Drive, Suite 100 Markham, ON, L3R 8B8 Phone 905 475 1900

More information

Using Hydraflow Storm Sewers Extension with AutoCAD Civil 3D 2008: A Recommended Workflow

Using Hydraflow Storm Sewers Extension with AutoCAD Civil 3D 2008: A Recommended Workflow AutoCAD Civil 3D 2008 Using Hydraflow Storm Sewers Extension with AutoCAD Civil 3D 2008: A Recommended Workflow The ability to perform storm water hydrology and hydraulic (H&H) tasks is crucial to civil

More information

Preliminary Servicing & Stormwater Management Report

Preliminary Servicing & Stormwater Management Report Prepared By: Hart Subdivision, City of Guelph Preliminary Servicing & Stormwater Management Report GMBP File: 112-155 May 22, 2015 GUELPH OW EN SOUND LISTOW EL KITCHENER EXETER HAMILTON GTA 650 W OODLAW

More information

Standard Site Drainage and Erosion Control Details (August 15, 2006)

Standard Site Drainage and Erosion Control Details (August 15, 2006) City of St. Petersburg Construction Services and Permitting Standard Site Drainage and Erosion Control Details (August 15, 2006) Attached are the City Engineer s approved City standards dated September

More information

SECTION 08000 STORM DRAINAGE TABLE OF CONTENTS

SECTION 08000 STORM DRAINAGE TABLE OF CONTENTS SECTION 08000 STORM DRAINAGE 08010 DESIGN A. Location B. Sizing TABLE OF CONTENTS 08020 MATERIALS A. Pipe Materials B. Structure Materials C. Installation D. Inlets and Outlets 08030 INSPECTIONS AND TESTING

More information

CITY UTILITIES DESIGN STANDARDS MANUAL

CITY UTILITIES DESIGN STANDARDS MANUAL CITY UTILITIES DESIGN STANDARDS MANUAL Book 2 (SW) SW9 June 2015 SW9.01 Purpose This Chapter provides information for the design of open channels for the conveyance of stormwater in the City of Fort Wayne.

More information

INFRASTRUCTURE DESIGN STANDARDS

INFRASTRUCTURE DESIGN STANDARDS Prepared by: IBI Group June 2011 Caution to Users: These standards are modelled after the City of London Subdivision and Development Design Guidelines and are done so recognizing the proximity of Middlesex

More information

DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES 33 00 00 SITE UTILITIES

DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 33 UTILITIES 33 00 00 SITE UTILITIES SECTION INCLUDES Domestic Water Fire Water Service Water Well Sanitary Sewer Storm Drains Foundation Drainage RELATED SECTIONS 03 30 00 Concrete 21 00 00 Fire Suppression - Sprinklers 22 00 00 Plumbing

More information

The value of the wastewater flow used for sewer design is the daily peak flow. This can be estimated as follows:

The value of the wastewater flow used for sewer design is the daily peak flow. This can be estimated as follows: This Section presents the theory of simplified sewer design. Firstly, in Section 2.1, the peak daily wastewater flow in the length of sewer being designed is described. Section 2.2 presents the trigonometric

More information

STAFF REPORT TO COMMITTEE OF THE WHOLE

STAFF REPORT TO COMMITTEE OF THE WHOLE STAFF REPORT TO COMMITTEE OF THE WHOLE DATE: November 7 2012 TO: FROM: SUBJECT: ATTACHMENT(S): COMMITTEE OF THE WHOLE GINA LAYTE-LISTON, SUPERVISOR, WASTEWATER Stormwater Management Funding Strategy None

More information

CHAPTER 17: STORM SEWER STANDARDS. 17.00 Introduction. 17.01 Administration. 17.02 Standards 17.1

CHAPTER 17: STORM SEWER STANDARDS. 17.00 Introduction. 17.01 Administration. 17.02 Standards 17.1 CHAPTER 17: STORM SEWER STANDARDS 17.00 Introduction 17.01 Administration 17.02 Standards 17.1 17.00 INTRODUCTION The purpose of this chapter is to provide guidance for the design and construction of storm

More information

STORM DRAINS CHAPTER 7

STORM DRAINS CHAPTER 7 CHAPTER 7 Chapter 7 - Storm Drains A storm drain is a drainage system that conveys water or stormwater, consisting of two or more pipes in a series connected by one or more structures. Storm drains collect

More information

For the purpose of this environmental compliance approval, the following definitions apply:

For the purpose of this environmental compliance approval, the following definitions apply: Ministry of the Environment Ministère de l Environnement ENVIRONMENTAL COMPLIANCE APPROVAL NUMBER 4126-8RYRF9 Issue Date: May 8, 2012 Quinte Healthcare Corporation 265 Dundas Street East Belleville, Ontario

More information

H. Khalid Jamil 9367 Verain Street San Diego, CA, 92129 (858) 663-9200

H. Khalid Jamil 9367 Verain Street San Diego, CA, 92129 (858) 663-9200 OFFSITE DRAINAGE REPORT Ramona Assisted Living 1236 "D" Street Ramona, CA 92065 re~*7lb3 Prepared for H. Khalid Jamil 9367 Verain Street San Diego, CA, 92129 (858) 663-9200 July 1 1, 2008 Daniel Tobar,

More information

SECTION 5: SANITARY SEWER SYSTEM DESIGN

SECTION 5: SANITARY SEWER SYSTEM DESIGN SECTION 5: SANITARY SEWER SYSTEM DESIGN 5.01 GENERAL Sanitary sewer improvements shall be designed to serve the ultimate level of City development as defined in the General Plan and the Wastewater Facilities

More information

City of West Linn Public Works Design Standards 2010. Table of Contents

City of West Linn Public Works Design Standards 2010. Table of Contents City of West Linn Public Works Design Standards Table of Contents SECTION TWO STORM DRAIN REQUIREMENTS... 1 2.0000 STORM DRAINS... 1 2.0010 General Design Requirements...1 2.0011 Site Drainage Plans...2

More information

Design Specifications & Requirements Manual

Design Specifications & Requirements Manual 3 SANITARY SEWER COLLECTIONS 3.1 DEFINITION... 1 3.1.1 Public Sewage Systems... 1 3.1.2 Private Sewage Systems... 1 3.2 NON-PERMITTED FLOWS... 1 3.3 LOCATION AND ALIGNMENT... 1 3.3.1 Sanitary Sewers on

More information

Town of Greenville Policy

Town of Greenville Policy Town of Greenville Policy Piping/Filling in of Roadside Ditches The Town owns its road right of way, not the abutting landowner. Purpose of Town roadside ditches: Town roadside ditches perform three primary

More information

Basic Hydrology. Time of Concentration Methodology

Basic Hydrology. Time of Concentration Methodology Basic Hydrology Time of Concentration Methodology By: Paul Schiariti, P.E., CPESC Mercer County Soil Conservation District What is the Time of Concentration? The time it takes for runoff to travel from

More information

WESTFIELD-WASHINGTON ADVISORY PLAN COMMISSION December 7, 2015 1512-SPP-24 & 1512-ODP-24

WESTFIELD-WASHINGTON ADVISORY PLAN COMMISSION December 7, 2015 1512-SPP-24 & 1512-ODP-24 Petition Number: Subject Site Address: Petitioner: Request: East side of Oak Road, north of 151 st Street Langston Development Co. Primary Plat and Overall Development Plan amendment review for Mapleridge

More information

The checklist utilized by the Authority will be similar to that which is shown below. Project Name: Location: Consulting Engineering Firm:

The checklist utilized by the Authority will be similar to that which is shown below. Project Name: Location: Consulting Engineering Firm: Page 1 of 6 Section 1. PURPOSE This policy is an Engineering checklist of the Local Review Program for sanitary sewer improvement projects by the Bedford Regional Water Authority ( Authority ). Section

More information

APPENDIX 9 INFRASTRUCTURE SERVICING REPORT

APPENDIX 9 INFRASTRUCTURE SERVICING REPORT APPENDIX 9 INFRASTRUCTURE SERVICING REPORT Lot 50 Cockram Street, Mundijong Infrastructure Servicing Report Peet Ltd August 2012 LOT 50 COCKRAM STREET, MUNDIJONG-INFRASTRUCTURE SERVICING REPORT Project

More information

2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS

2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS 2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS Water system improvements proposed for inclusion into Western s service area shall be designed in accordance with all appropriate AWWA standards, include

More information

2015 Water and Wastewater Rates and Service Fees

2015 Water and Wastewater Rates and Service Fees STAFF REPORT ACTION REQUIRED 2015 Water and Wastewater Rates and Service Fees Date: January 13, 2015 To: From: Wards: Reference Number: Budget Committee Deputy City Manager and Chief Financial Officer

More information

Travel Time. Computation of travel time and time of concentration. Factors affecting time of concentration. Surface roughness

Travel Time. Computation of travel time and time of concentration. Factors affecting time of concentration. Surface roughness 3 Chapter 3 of Concentration and Travel Time Time of Concentration and Travel Time Travel time ( T t ) is the time it takes water to travel from one location to another in a watershed. T t is a component

More information

CONSTRUCTION STORMWATER POLLUTION PREVENTION PLAN TEMPLATE

CONSTRUCTION STORMWATER POLLUTION PREVENTION PLAN TEMPLATE CONSTRUCTION STORMWATER POLLUTION PREVENTION PLAN TEMPLATE The following template may be used as a general guide for development of a Stormwater Pollution Prevention Plan (SWPPP) for construction activities.

More information

APPENDIX C INLETS. The application and types of storm drainage inlets are presented in detail in this Appendix.

APPENDIX C INLETS. The application and types of storm drainage inlets are presented in detail in this Appendix. Storm Drainage 13-C-1 APPENDIX C INLETS 1.0 Introduction The application and types of storm drainage inlets are presented in detail in this Appendix. 2.0 Inlet Locations Inlets are required at locations

More information

APPENDIX M-2 SANITARY SEWER TECHNICAL MEMORANDUM. Stadium Reconstruction EIR

APPENDIX M-2 SANITARY SEWER TECHNICAL MEMORANDUM. Stadium Reconstruction EIR APPENDIX M-2 SANITARY SEWER TECHNICAL MEMORANDUM Stadium Reconstruction EIR Appendices \ AECOM Technical Services, Inc 401 West A Street Suite 1200 San Diego, CA 92101 www.aecom.com 619-610-7600 tel 619-610-7601

More information

Lisgar District Basement Water Infiltration Investigation Answers to Residents Written Questions Received by Councillors Ward 10 Office

Lisgar District Basement Water Infiltration Investigation Answers to Residents Written Questions Received by Councillors Ward 10 Office Lisgar District Basement Water Infiltration Investigation Part A Answers to Technical Questions 1. There has been a tremendous amount of work done everywhere along the creek. If there was nothing wrong

More information

SEWER LINE EXTENSION DESIGN CHECKLIST

SEWER LINE EXTENSION DESIGN CHECKLIST SEWER LINE EXTENSION DESIGN CHECKLIST SWLE# Utilities Staff Date DISCLAIMER - This checklist is provided to Consulting Engineers for the express purpose of assisting them in compiling design plans for

More information

TOPOGRAPHICAL SURVEY REPORT - PART OF L.R No. 7413/11 Done on February 2015 at International Union for Conservation of Nature (IUCN) Eastern African

TOPOGRAPHICAL SURVEY REPORT - PART OF L.R No. 7413/11 Done on February 2015 at International Union for Conservation of Nature (IUCN) Eastern African TOPOGRAPHICAL SURVEY REPORT - PART OF L.R No. 7413/11 Done on February 2015 at International Union for Conservation of Nature (IUCN) Eastern African Regional Office 01 CHAPTER ONE Checklist Page 2 of 8

More information

APPENDIX D INLET CAPACITY AND SPACING. The capacity and spacing design of storm drainage inlets are presented in detail in this Appendix.

APPENDIX D INLET CAPACITY AND SPACING. The capacity and spacing design of storm drainage inlets are presented in detail in this Appendix. Storm Drainage 3-D- PPENDIX D INET CPCITY ND SPCING.0 Introduction The capacity and spacing design of storm drainage inlets are presented in detail in this ppendix. 2.0 Design Recurrence Interval and Spread

More information

CHAPTER 11 STORM DRAINAGE

CHAPTER 11 STORM DRAINAGE CHAPTER STORM DRAINAGE SECTION PC 0 GENERAL 0. Scope. The provisions of this chapter shall govern the materials, design, construction and installation of storm drainage. Storm water discharge shall be

More information

Chapter 5.0. Stormwater Credits for Innovative Site Planning

Chapter 5.0. Stormwater Credits for Innovative Site Planning Chapter 5.0 Stormwater Credits for Innovative Site Planning Chapter 5. Stormwater Credits...Introduction 5.0 Stormwater Credits In Maryland, there are many programs at both the State and local level that

More information

City of Colleyville Community Development Department. Site/Landscape Plan Application Packet

City of Colleyville Community Development Department. Site/Landscape Plan Application Packet City of Colleyville Community Development Department Site/Landscape Plan Application Packet Development Application Fees City of Colleyville 100 Main Street Colleyville TX 76034 817.503.1050 Zoning Zoning

More information

URBAN STORMWATER GUIDELINES AND BEST MANAGEMENT PRACTICES FOR PROTECTION OF FISH AND FISH HABITAT DRAFT DISCUSSION DOCUMENT

URBAN STORMWATER GUIDELINES AND BEST MANAGEMENT PRACTICES FOR PROTECTION OF FISH AND FISH HABITAT DRAFT DISCUSSION DOCUMENT URBAN STORMWATER GUIDELINES AND BEST MANAGEMENT PRACTICES FOR PROTECTION OF FISH AND FISH HABITAT DRAFT DISCUSSION DOCUMENT Contacts: Barry Chilibeck (666-3765) or Megan Sterling (666-2322) Revision 4

More information

STORMWATER POLLUTION PREVENTION PLAN TEMPLATE. 1.0 SITE DESCRIPTION 1.1 Project Name and Location Date

STORMWATER POLLUTION PREVENTION PLAN TEMPLATE. 1.0 SITE DESCRIPTION 1.1 Project Name and Location Date STORMWATER POLLUTION PREVENTION PLAN TEMPLATE Disclaimer: This template was developed for guidance purposes only in an effort to assist Construction Storm Water permit applicants in meeting state and local

More information

BLACK/HARMONY/FAREWELL CREEK WATERSHED EXISTING CONDITIONS REPORT CHAPTER 12 - STORMWATER MANAGEMENT

BLACK/HARMONY/FAREWELL CREEK WATERSHED EXISTING CONDITIONS REPORT CHAPTER 12 - STORMWATER MANAGEMENT Harmony Creek subwatershed Harmony Creek subwatershed BLACK/HARMONY/FAREWELL CREEK WATERSHED EXISTING CONDITIONS REPORT CHAPTER 12 - STORMWATER MANAGEMENT April 2011 TABLE OF CONTENTS 1.0 INTRODUCTION...

More information

THE APPRAISAL OF REAL ESTATE 3 RD CANADIAN EDITION BUSI 330

THE APPRAISAL OF REAL ESTATE 3 RD CANADIAN EDITION BUSI 330 THE APPRAISAL OF REAL ESTATE 3 RD CANADIAN EDITION BUSI 330 REVIEW NOTES by CHUCK DUNN CHAPTER 10 Copyright 2010 by the Real Estate Division and Chuck Dunn. All rights reserved ARE 3 rd EDITION REVIEW

More information

SECTION 7- STORM SEWER

SECTION 7- STORM SEWER SECTION 7- STORM SEWER 7.1. STORM SEWERS.... 7-1 7.2. SUMP DRAINS... 7-3 7.3. CATCH BASINS... 7-3 7.4. MANHOLES... 7-4 7.5. STORM SEWER CALCULATIONS... 7-4 7.6. CULVERTS AND BRIDGES... 7-5 7.7. OPEN CHANNELS...

More information

Rational Method Hydrologic Calculations with Excel. Rational Method Hydrologic Calculations with Excel, Course #508. Presented by:

Rational Method Hydrologic Calculations with Excel. Rational Method Hydrologic Calculations with Excel, Course #508. Presented by: Rational Method Hydrologic Calculations with Excel, Course #508 Presented by: PDH Enterprises, LLC PO Box 942 Morrisville, NC 27560 www.pdhsite.com Calculation of peak storm water runoff rate from a drainage

More information

Interlocking Concrete Pavement Institute (ICPI) Model Stormwater Ordinance for Permeable Interlocking Concrete Pavements August 2010

Interlocking Concrete Pavement Institute (ICPI) Model Stormwater Ordinance for Permeable Interlocking Concrete Pavements August 2010 Interlocking Concrete Pavement Institute (ICPI) Model Stormwater Ordinance for Permeable Interlocking Concrete Pavements August 2010 Background What are permeable interlocking concrete pavements (PICP)?

More information

Electronic Signature and Fee Payment Confirmation

Electronic Signature and Fee Payment Confirmation Jeff Levine, AICP, Director Planning & Urban Development Department Electronic Signature and Fee Payment Confirmation Notice: Your electronic signature is considered a legal signature per state law. By

More information

Newbiggin House Farm,

Newbiggin House Farm, Newbiggin House Farm, Near Waberthwaite Flood Investigation Report 32 Flood Event 30/8/2012 Cumbria County Council Version Undertaken by Reviewed by Approved by Date Preliminary Colin Parkes Anthony Lane

More information

West Thornhill Stormwater Flood Remediation Phase 1 Construction. Community Information Meeting

West Thornhill Stormwater Flood Remediation Phase 1 Construction. Community Information Meeting West Thornhill Stormwater Flood Remediation Phase 1 Construction Community Information Meeting Thornhill C.C. May 7, 2014 Purpose To advise residents and businesses of 2014 and 2015 construction activities

More information

CHAPTER 5. Storm Sewer

CHAPTER 5. Storm Sewer CHAPTER 5 Storm Sewer A. Introduction All proposed developments shall have a properly designed and constructed storm water conveyance system. This chapter deals only with the conveyance system. Storm water

More information

DECISION/DIRECTION NOTE

DECISION/DIRECTION NOTE DECISION/DIRECTION NOTE Title: Proposed rezoning new residential zone PDE file MPA1500006 150 Stavanger Drive Date Prepared: April 12, 2016 Report To: Chair and Members, Planning and Development Committee

More information

Pioneer Park Stormwater Management Rehabilitation Project Town of Richmond Hill Engineering and Public Works Department Design, Construction and

Pioneer Park Stormwater Management Rehabilitation Project Town of Richmond Hill Engineering and Public Works Department Design, Construction and Pioneer Park Stormwater Management Rehabilitation Project Town of Richmond Hill Engineering and Public Works Department Design, Construction and Water Resources Division Presentation Outline Background

More information

Agenda Item # Page iy PLANNING COMMITTEE R. PANZER GENERAL MANAGER OF PLANNING &DEVELOPMENT

Agenda Item # Page iy PLANNING COMMITTEE R. PANZER GENERAL MANAGER OF PLANNING &DEVELOPMENT Agenda Item # Page iy PLANNING COMMITTEE R. PANZER GENERAL MANAGER OF PLANNING &DEVELOPMENT APPLICATION BY: CROWN DEVELOPMENT LTD. 1777 HIGHBURY AVENUE NORTH That on the recommendation of the General Manager

More information

Functional Servicing and Preliminary Stormwater Management Report Paris Grand Submission

Functional Servicing and Preliminary Stormwater Management Report Paris Grand Submission Functional Servicing and Preliminary Stormwater Management Report Paris Grand Submission GolfNorth Properties 400 Golf Course Road Conestoga, ON N0B1N0 R.J. Burnside & Associates Limited 6990 Creditview

More information

ORDINANCE NO. 2013 -

ORDINANCE NO. 2013 - ORDINANCE NO. 2013 - AN ORDINANCE OF BREVARD COUNTY, FLORIDA AMENDING CHAPTER 62, LAND DEVELOPMENT REGULATIONS SECTION 62-2891, LOT DRAINAGE, AND CHAPTER 22 BUILDINGS AND BUILDING REGULATIONS, SECTION

More information

CITY OF FARMERSVILLE, TEXAS

CITY OF FARMERSVILLE, TEXAS CITY OF FARMERSVILLE, TEXAS MANUAL FOR THE DESIGN OF WATER AND SANITARY SEWER LINES Subdivision Ordinance #2007-08 Exhibit B February 13, 2007 TABLE OF CONTENTS Description Page No. General... 1 Water

More information

The City of STORM DRAINAGE SYSTEM Section 12 Grande Prairie Page 1 of 41 SECTION 12 STORM DRAINAGE SYSTEM

The City of STORM DRAINAGE SYSTEM Section 12 Grande Prairie Page 1 of 41 SECTION 12 STORM DRAINAGE SYSTEM Grande Prairie Page 1 of 41 1. GENERAL SECTION 12 STORM DRAINAGE SYSTEM The storm sewers shall be designed as a separate system and consider both the minor and major drainage. There shall be of sufficient

More information

Permeable Interlocking Concrete Pavements. The Stormwater Problem

Permeable Interlocking Concrete Pavements. The Stormwater Problem Permeable Interlocking Concrete Pavements The Stormwater Problem 1 Stormwater Management Objectives Water Quantity Accommodate water volumes & peak flows Water Quality Control pollutant levels A Low Impact

More information

2.1 Development of Risk-Based Asset Management Framework

2.1 Development of Risk-Based Asset Management Framework SECTION 2 Development of Asset Management Framework 2.1 Development of Risk-Based Asset Management Framework As part of the master planning effort, WES developed a risk-based asset management framework

More information

Town of Beaumont. Lot Grading Guidelines

Town of Beaumont. Lot Grading Guidelines Town of Beaumont Lot Grading Guidelines LOT GRADING APPROVAL PROCESS Lot Grading Guidelines... 3 Introduction... 3 Purpose... 3 Definitions... 3 Lot Grading... 3 Lot Grading Plan... 3 Lot Grading Certificate...

More information

Model Subdivision and Land Development (SALDO) Subdivision/ Land Development Presentation Overview. Why Subdivision and Land Development Regulations?

Model Subdivision and Land Development (SALDO) Subdivision/ Land Development Presentation Overview. Why Subdivision and Land Development Regulations? Model Subdivision and Land Development (SALDO) Subdivision/ Land Development Presentation Overview Purpose of Subdivision/ Land Development Ordinances (SALDO) Municipalities Planning Code Process Design

More information

DOÑA ANA COUNTY DESIGN STORM CRITERIA GUIDELINES FOR COMMERCIAL AND RESIDENTIAL SITES. Run-off Analysis Methods

DOÑA ANA COUNTY DESIGN STORM CRITERIA GUIDELINES FOR COMMERCIAL AND RESIDENTIAL SITES. Run-off Analysis Methods DOÑA ANA COUNTY DESIGN STORM CRITERIA GUIDELINES FOR COMMERCIAL AND RESIDENTIAL SITES Run-off Analysis Methods This document sets forth the minimum design, technical criteria and specifications for the

More information

Town of Elkton & Cecil Soil Conservation District Checklist for Joint Agency Review Stormwater Management / Erosion and Sediment Control

Town of Elkton & Cecil Soil Conservation District Checklist for Joint Agency Review Stormwater Management / Erosion and Sediment Control Town of Elkton & Cecil Soil Conservation District Checklist for Joint Agency Review Stormwater Management / Erosion and Sediment Control Project Name: Tax Map Parcel: Acreage: Plat: ADC Map & Grid Engineering

More information

Module 7: Hydraulic Design of Sewers and Storm Water Drains. Lecture 7 : Hydraulic Design of Sewers and Storm Water Drains

Module 7: Hydraulic Design of Sewers and Storm Water Drains. Lecture 7 : Hydraulic Design of Sewers and Storm Water Drains 1 P age Module 7: Hydraulic Design of Sewers and Storm Water Drains Lecture 7 : Hydraulic Design of Sewers and Storm Water Drains 2 P age 7.1 General Consideration Generally, sewers are laid at steeper

More information

Index. protection. excavated drop inlet protection (Temporary) 6.50.1 6.51.1. Block and gravel inlet Protection (Temporary) 6.52.1

Index. protection. excavated drop inlet protection (Temporary) 6.50.1 6.51.1. Block and gravel inlet Protection (Temporary) 6.52.1 6 Index inlet protection excavated drop inlet protection (Temporary) 6.50.1 HARDWARE CLOTH AND GRAVEL INLET PROTECTION Block and gravel inlet Protection (Temporary) sod drop inlet protection ROCK DOUGHNUT

More information